Description
Features
- Pure, filtered DC power source for the highest accuracy readings
- Highest Accuracy and Precision of any high current test system
- Complete, automatic calibration system and self-diagnostics
- Automatic measurements of low resistance from 0.01 µΩ … 5 Ω
- Microprocessor-based system with internal storage for over 2,000 test results
- Single or continuous measurements with automatic data storage
- Preset a number of tests, at various timed intervals, for automatic data storage
- Cable length correction for Cable Manufacturer
- Internal printer
- Printing and storaging of test results while the test system is measuring
- Standard centronics (parallel) interface & RS-232 (serial) interface
- Automatic, high efficiency cooling system to dissipate internal heat
- Automatic shut off for over-temperature conditions
- Panel-mounted emergency stop switch
- LCD with a backlight
- Wide input power source range
- Lightweight and portable, less than 14.5 kg (33 Lbs.)
- 5-Year standard warranty
Accuracy
Current Range | Measuring Range | Accuracy | Resolution |
200A | 0.00 µΩ … 20 mΩ | ± 0.1% Rdg ± 0.01 µΩ | 5 Digits or 0.01 µΩ |
100A | 0.00 µΩ … 40 mΩ | ± 0.1% Rdg ± 0.02 µΩ | 5 Digits or 0.02 µΩ |
50A | 0.00 µΩ … 100 mΩ | ± 0.1% Rdg ± 0.04 µΩ | 5 Digits or 0.05 µΩ |
20A | 0.0 µΩ … 1.0 Ω | ± 0.1% Rdg ± 0.1 µΩ | 5 Digits or 0.1 µΩ |
10A | 0.0 µΩ … 5.0 Ω | ± 0.1% Rdg ± 0.2 µΩ | 5 Digits or 0.2 µΩ |
Resistance Range: | 0.00 µΩ to 5 Ω |
Measuring duty cycle: | 200A: 10 min. on, 2 min. off 100A and below: continuous |
Temperature: | Operating: -10ºC to 60°C (14ºF to 140ºF) Storage: -20°C to 70°C (-4ºF to 158ºF) |
Specifications
- Size: L: 521 mm (20.5″) W: 432 mm (17″) H: 216 mm (8.5″)
- Weight: 14.4 kg (31.5 lbs)
- Input Power: 100 to 250 VAC, 50/60 Hz, auto ranging
- Output Power: 1000 Watt
- Resistance Range: 0.01 µΩ … 5 Ω
- Test Current: User Selectable: 200, 100, 50, 20, 10A DC
- Panel Display: LCD graphic with a backlight
- Front Panel: Sealed, anodized with a multi-actuation rotary knob
- Interface: 9 Pin RS-232 serial / 25 Pin Centronics parallel
- Internal printer
- Memory Storage: internally stores up to 2,000 test results
- Temperature: Operating: –10°C to 60°C (14ºF to 140ºF), Storage: –20°C to 70°C (-4ºF to 158ºF)
Options
- 2021N-26001: Temperature Probe – 10m (32 ft.)
- 2021N-15001: Annual Warranty Extension
Downloads
Firmware MC2 (1.30)
Flyer MC2
Temperature Probe Flyer
Instruction Manual MC2 (2.2)
MC2 Command Set (1.04)