Description
Dimensions
- Product Net Width:
- 105 mm
- Product Net Height:
- 150 mm
- Product Net Depth / Length:
- 70 mm
- Product Net Weight:
- 1.6 kg
Container Information
- Package Level 1 Units:
- box 1 piece
- Package Level 1 Width:
- 155 mm
- Package Level 1 Height:
- 190 mm
- Package Level 1 Depth / Length:
- 155 mm
- Package Level 1 Gross Weight:
- 1.7 kg
- Package Level 1 EAN:
- 8015644790899
Environmental
- RoHS Status:
- Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Technical UL/CSA
- Interrupting Rating acc. to UL489:
- (240 V AC) 50 kA
(480 V AC) 25 kA
(600Y / 347 V AC) 10 kA
(250 V DC) 2 Poles in Series 25 kA
(500 V DC) 3 Poles in Series 25 kA
Additional Information
- Circuit Breaker Type to be Associated:
- Power Distribution
- Current Type:
- AC/DC
- Electrical Durability:
- 120 cycles per hour
8000 cycle
- Mechanical Durability:
- Nr. Operations 240 cycles per hour
Nr. Operations 25000 cycle
- Number of Poles:
- 3
- Opening Time:
- CB with SOR 15 ms
CB with UVR 15 ms
- Order Multiple:
- 1 piece
- Power Loss:
- at Rated Operating Conditions per Pole 4.5 W
- Product Main Type:
- SACE Tmax XT
- Product Name:
- Moulded Case Circuit Breaker
- Product Type:
- CB
- Rated Current (In):
- 90 A
- Rated Voltage (Ur):
- 600Y/347 V
- Rated Instantaneous Short-Circuit Current Setting (Ii):
- 900 A
- Rated Operational Voltage:
- 600Y/347 V AC
500 V DC
- Rated Uninterrupted Current (Iu):
- 225 A
- Release:
- TMF
- Release Type:
- TM
- Setting Range:
- 90 A
- Short-Circuit Performance Level:
- N
- Standards:
- UL
- Sub-type:
- XT3
- Suitable for Product Class:
- SACE Tmax XT
- Terminal Connection Type:
- Fixed Circuit-Breakers
- Version:
- F
- CAD Dimensional Drawing:
- 1SDH001295R0409
- Mechanical Drawings:
- 1SDH000720R0100
- Wiring Diagram:
- 1SDM000068R0001
Certificates and Declarations (Document Number)
- Data Sheet, Technical Information:
- 1SDC210200D0206
1SDC210199D0206
- Declaration of Conformity – CE:
- 9AKK106713A5530
- Environmental Information:
- 9AKK107991A8215
- Instructions and Manuals:
- 1SDH000720R0003
- REACH Declaration:
- 9AKK108466A1425
- RoHS Information:
- 9AKK108466A1424
Classifications
- ETIM 4:
- EC000228 – Power circuit-breaker for trafo/generator/installation prot.
- ETIM 5:
- EC000228 – Power circuit-breaker for trafo/generator/installation prot.
- ETIM 6:
- EC000228 – Power circuit-breaker for trafo/generator/installation prot.
- ETIM 7:
- EC000228 – Power circuit-breaker for trafo/generator/installation protection
- ETIM 8:
- EC000228 – Power circuit-breaker for trafo/generator/installation protection
- WEEE Category:
- 5. Small Equipment (No External Dimension More Than 50 cm)
- eClass:
- V11.1 : 27370409