Description
Features
- Extended test voltage measurement range of up to 250V
- Automatic measurements of Voltage, Turns Ratio, Current and Phase displacement
- Easy one-time hook up to the transformer
- Automatic test voltage range
- Displays deviation from a nominal ratio
- Tap changer interface with graphic results
- Load on test object <0.05 VA
- Measures Power transformers, PTs and CTs
- Automatic vector group detection
- Enhanced heavy-duty protection circuitry
- Emergency stop button immediately turns off output
- Data storage for more than 10,000 measurements
- Simple-to-operate color LCD touch screen with back light
- Two USB interfaces
- 5-Year standard warranty
Accuracy
Range | Accuracy at 100V or 40V | Accuracy at 10V | Resolution |
0.8 … 2,000 | ±0.06% Rdg ±1 LSD | ±0.15% Rdg ±1 LSD | 5 Digits |
2,001 … 4,000 | ±0.1% Rdg ±1 LSD | ±0.3% Rdg ±1 LSD | 5 Digits |
4,001 … 13,000 | ±0.3% Rdg ±1 LSD | not specified | 5 Digits |
13,001 … 16,000 | ±0.4% Rdg ±1 LSD | 5 Digits | |
Range | Accuracy at 250V | Resolution | |
0.8 … 5,000 | ±0.06% Rdg ±1 LSD | 5 Digits | |
5,001 … 10,000 | ±0.1% Rdg ±1 LSD | 5 Digits | |
10,001 … 32,500 | ±0.3% Rdg ±1 LSD | 5 Digits | |
32,501 … 45,000 | ±0.4% Rdg ±1 LSD | 5 Digits | |
Current | Accuracy | Resolution | |
0 … 1A | ±0.001A | 0.1mA | |
Phase Angle | Accuracy | Resolution | |
±90 Degree | ±0.05 Degree | 0.01 Degree | |
Turns Ratio Range | 0.8 to 45,000 | ||
Temperature | Operating: -10ºC to 60°C (14ºF to 140ºF) Storage: -20°C to 70°C (-4ºF to 158ºF) |
See Instruction Manual for more parameters. Specifications subject to improvement at any time.
Specifications
- Size: L: 490 mm (19.3″) W: 436 mm (17.2″) H: 177 mm (7″), Rack Unit: 4U
- Weight: 7.8 kg (17 lbs.)
- Input Power: 100 to 250 VAC, 50/60 Hz auto ranging. Fuse: 2A
- Test Voltage: User Selectable: 250, 100, 40, 10, and 1 VAC
- Max test current: 1A
- Panel Display: Color LCD with a back light and a touch screen
- Front Panel: Sealed, anodized
- Interface: 4 USB 1.1 (3 host/1 device) and 9 Pin RS-232 serial
- Memory Storage: Internally stores more than 10,000 test results
- Temperature: Operating: –10°C to 60°C (14ºF to 140ºF), Storage: –20°C to 70°C (-4ºF to 158ºF)
Accessories
- 1002A-05015: H and X Lead Set – 5m (16ft.)
- 1002A-05023: H and X Extensions – 10m (32 ft.)
- 1002A-07001: Power Cord – 6.09m (20ft.)
- 1011A-05013: Ground Lead – 5m (16ft.)
- 1003A-37001: A-B USB Cable – 3.05m (10ft).
- 2020A-23001: RS-232 Cable – 3.05m (10ft.)
- 1004A-27003: External USB Drive
- 1003A-02002: Instruction Manual
- 2040A-08003: Touch Screen Stylus
- 2042A-03001: External Zippered Pouch
- 1002X-07001: Spare Fuse Set, Time Delay 2A (Qty. 5)
- 2040A-03003: Cable Bag
Options
• 1003N-31001: External Trigger Switch for Tap Changer Testing
• 1002A-05002: Red Extension Cable – 10m (32 ft.)
• T-Rex R: 3 Phase Test Voltage Option for TR-Mark III R 250V
• TR-Mark III 250V: Field Case Version
• 1004N-15002: Annual Warranty Extension
Downloads
TR-Mark III (v3.2.2.0)
Flyer TR-Mark III
Command Set TR-Mark III (0.05)
Instruction Manual TR-Mark III 250V (v1.10)
T-Base Pro (2.4.0)